Soft Starters

Why soft starters?

Reactor based soft starters by reducing the heating caused by frequent start/stops, reducing the mechanical stress on the motor and its shaft, and reducing the electro dynamic stresses on the power cables, soft starters will protect your electric motor from possible damage while also extending the lifespan of your electric motor and the entire system.

Are you facing same problems with existing motor starting solution? Wants modern FCMAplus based soft starter? then stop searching you are on your destination.

iEngineering group can provide one of the best customize motors starting Solutions. We can supply L.T & H.T Soft Starters which are FCMAplus technology based and complying with AS/NZS 60076-6 standard. We have LT & HT FCMA type, reactor based Soft Starters up to 20 MV, 13.8 kV, and 50/60 HZ. We serve all major industries like Water treatment & water supply, Steel plants, Infrastructure & HVAC, Pharmacy industries, oil & gas, Fertilizers, Automobiles, Textiles, Paper mills.

Difference between Electronic soft starter and FCMAPlus/HFSRPlus soft starter

Sr. No. Parameters Electronic Soft Starter FCMAPlus/HFSRPlus Soft starter
1
Operation Principle of
Using Thyristor / IGBT/MOSFET Control; power electronic device will cut the sine wave disturbing the fundamental frequency of the sine wave.
Reduced Voltage by potential divider action. Motor voltage increases gradually with speed up to 95%. Final bypass to full voltage. Only Amplitude control, so no harmonics.
2
Starting Current
Starting current is higher in the range of 3.5 - 4 times the full load current, and cannot achieve a lower starting current of 1-1.5 times the full load current
Starting current is reduced to the minimum theoretical value as no current is wasted in harmonics. The entire current is at fundamental frequency. With the offered FCMAPlus/HFSRPlus soft starting solution, the starting current can be reduced to 1 - 1.5Ifl.
3
Harmonics
Since the fundamental sine wave is disturbed, harmonics are generated, polluting the power system and damaging capacitors, Increased heating in motors etc.
FCMAPLUS/HFSRPlus are entirely Harmonics Free systems.
4
Maintenance
Electronics Technology obsolescence after 3-4 years. Spares are imported and costly mostly not available due to obsolescence. Hence heavy expenditure for the replacement.
No obsolescence. Simple and rugged system. No routine maintenance required.
5
Operation and Reliability
Power electronics components are prone to failure. Requires controlled cooling environment, thereby increasing the capital and running cost of the equipment.
Ensures high reliability. Can operate in the harsh environment; up to 50°C ambient temperatures, without any need of cooling.
6
Cost
Electronic soft starters are more cost effective in LV range.
Our reactor based soft starters are more competitive in HT range (3.3kV, 6.6kV and 11kV range). Installation cost is smaller than 10-15% than electronic soft starter.

Low Voltage FCMAplus soft starter

Our LV FCMAplus soft starters are air-core based series reactors, providing a complete starting solution for any motor application involving pumps, blowers, fans or compressors. We design customized solutions specific to each motor, analysing motor and load torque speed curves, current speed and moment of inertia.

Soft starters are provided with a bypass device (power contactor or air circuit breaker) of customer preferred make. When required by the customer, we offer a complete solution with motor feeder i.e. ACB /power contactor with MPR and metering for switching and protection purpose. All our starters are automated using a PLC with HMI which creates reliability.

The standard starting current committed by our soft starters is 3-3.5 times the full load current. We can also reduce the starting current up to 1 to 1.5 times the full load current if required by using a Dynamic Compensator.

Our LV soft starters offer the best competitive value for our customers and offer superior value than the conventional electronic soft starters.

Reactor based soft starters
Technical specification
Input Voltage
415V/690V
Motor Power Range
Up to 2,000 kW
Application
Pump, Compressor, Fan, Blower
Frequency
50Hz/60Hz
Temperature Operation Range
0°C to 55°C
Installation
Indoor
Cooling Method
Air Cooled
Insulation Class
Class F or customized
Standard
IEC 60076-6
Construction
Air Core, Vacuum Pressure Epoxy Impregnated
Conductor
Electrolytic Copper
Starting Current
Version 1: 3-3.5 times starting current Version 2: 1.5 times full load current with Dynamic Compensator
Reactor variation
5-tap design at 5% voltage difference at each tap

Medium Voltage FCMAplus soft starter

Our MV FCMAplus soft starters are air-core based series reactors, providing a complete starting solution for any motor application involving pumps, blowers, fans or compressors. We design customized solutions specific to each motor, analysing motor and load torque speed curves, current speed and moment of inertia.

Starting current will be reduced 3 to 3.5 x full load current (IFL) typically for any applications like pump, compressor, fans, blowers, mills. A standard product will be provided with the FCMAplus/HFSR soft starter with bypass vacuum contactor of customer preferred make or with a bypass vacuum circuit breaker. Our line-side soft starters are designed for fault level of the system. We use closed loop control using a PLC Line side soft starter are preferred for motors in hazardous area or when neutral terminal box is not available.

Reactor based soft starters

We use closed-loop control using a PLC Line side soft starter is preferred for motors in hazardous areas or when the neutral terminal box is not available.

power quality solution
Technical specification
Input Voltage
3.3 kV to 13.8 kV
Motor Power Range
200 kW to 20MW
Application
Pump, Compressor, Fan, Blower
Frequency
50Hz/60Hz
Temperature Operation Range
0°C to 55°C
Installation
Indoor
Cooling Method
Air Cooled
Insulation Class
Class F or customized
Standard
IEC 60076-6
Construction
Air Core, Vacuum Pressure Epoxy Impregnated
Conductor
Electrolytic Copper
Starting Current
Compensator Version 2: 1.5 times full load current with Dynamic Version 1: 3-3.5 times of full load current
Reactor variation
5-tap design at 5% voltage difference at each tap

The standard starting current committed by our soft starters is 3-3.5 times the starting current. We can also reduce the starting current up to 1 to 1.5 times the starting current if required by using a Dynamic Compensator.

Our MV soft starters offer the best competitive value for our customers and offer superior value than the conventional electronic soft starters.

Product Features

Why iEngineering Soft starter?

FCMAPlus/HFSRPlus Soft starter Other Soft Starter Manufacturers
Our VPI technology, unique amongst our competitors, allows for greater rigidity to our coils, to ensure each turn, layer and interstice is impregnated with resin, allowing for unmatched rigidity and insulation integrity. This indispensable feature allows for greater longevity of our soft starter’s vis-à-vis our competitors.
No VPI technology presents; results in poor rigidity of coils and lower longevity of starters.
We separate ourselves from the competition by measuring the impedance of the reactor coils which guarantees the starting current of the motor as promised to the customer. We follow strict quality norms outlined in AS/NZS 60076-6, IEC-60076-6, ensuring the customer receives accurate impedance measurement.
No measurement of Impedance; will result in inexact starting current as it is critical to accurate starting current prediction.
We offer versatile design with FIVE different voltage tap designs - Design Tap (DT) (DT +5%, DT +10%, DT +15%, and DT +20), as per AS 60034 IEC-60034 for starting current and starting torque, motor starter manufacturers specify design tolerance of 20% for starting current and torque. To have flexibility in accommodating variations in motor and driven equipment due to operating conditions, the tolerance is highly essential.
Our competitors offer a 3-tap design or a single tap design, thus offering an inferior flexibility when it comes to starting current selection of the motor. This results high bypass current.

Case Studies:-

  1. Shovel application for coal mines: –

    Motor rating – 560KW, 6.6KV, 59Amps

    Motor started with reactor based Soft starter – 100Amps

    Panel customized to fit in the available space inside the shovel (Vehicle)

    Starting current limited to 1.5 I_fl

  2. Iron and Steel Company: 

Transformer MVA: -11MVA, 11KV

Internal impedance: – 8%

Motor details -: 3.2MW, 11KV.

Base load – 225KW (Aux LT loads)

SI. No Model of Soft starter Starting current Seen by the Power System (A) Base Load in KW on Transformer before starting % Voltage drop Motor starting(kVA) % Over loading of 11 MVA transformer
1
DOL starting
6.5
225
19.43
24821
226%
Achieved parameters after commissioning
Starting with SS and support of PF correction of 2000KVAr
2.75
3450 ( 1 motor running with other base load 225KW)
7.2
10437
No Over loading

  3. Oil Exploration Site Captive Power Plant

Generator: – 10MVA, 0.8 PF since two generators are in parallel

Gen KW = 10*0.8 = 8 MW.

Gen KVAR = 10*0.6*1.4 = 8.4 MVAR, considering an overload of 40 % in reactive power.

Reciprocating Inlet Compressor motor

Compressor Rating 1: 1885 kW, 6600 V, 197.8 a full load current; DOL current: 650%.

Overhead Screw Compressor

Compressor Rating 2: 1350 kW, 6600V, 138.1A full load current; DOL current: 650%.

Site results of starting
SI. No
Model of Soft starter
Application
Starting current Seen by the Power System (A)
% Voltage drop
Acceleration time
Generator Capacity
1
1350- 2 Step SS with DC
Overhead compressor- SCREW COMPRESSOR
<2.5 Ifl
<2%
9 sec
2X5MW GTG
2
1885 2 Step SS with DC
Reciprocating compressor-Nitrogen feed gas
<2.5lfl
<2%
8Sec
2X5MW GTG

4. IRRIGATION PUMP: –

Transformer: – 31.5 MVA, 220KV/11KV, 10.5%

Motor: – 10.5 MW, 11KV, 562A, Synchronous

Application: – Pump

 

Starting Performance
Parameter
DOL
Commitment
At site
Ist
4.2 p.u,
3.0 p.u. (1686 A)
2.74 p.u. (1540 A)
Tst
2-3 sec
12- 13 sec
10-11 sec
V drop
15%
<10%
9%
Starting kVA
44,970 KVA
32,000 KVA
29,340 KVA
Xmer Loading
1.43 p,u,
1 p,u,
0.93 p,u,

5. Steel plant blower

Motor Details: Frame – YKS-800-4 Motor – 4550 KW, 6600V, 1493 rpm .

Blower: – Flow rate 1330 m3/min, For Sinter plant.

Power Transformer: – 20 MVA with int imp – 10.3%

FCMA-Soft starter Model No: – FCMA- N-4500-6.6KV-40KA1-01-HD.

Starting Performance
Parameter
Commitment
At site
Ist
3.5xIFL( 889A),
3xIFL( 762 A)
Tst
45 Sec
34 sec
V drop
Less than 1100 Volts (10%),
Actual 750 Volts (6.38%)

6. Steel plant

Soft Starter is based on Series reactor principle as per IS5553 Part-3/IEC60289 (old standard), IEC60076-6.

Motor: – 4200KW, 11KV, 50Hz, 1500rpm, Full.

Load current: – 254 Amps.

Application: – Waste gas Fan.

Grid Capacity: – Starting Current: – Committed – 3.5x I-FL (889A), Actual 3xIFL (762 A)

Voltage drop: – Committed – less than 1100 Volts (10%), Actual 750 Volts (6.38%)

Starting Time: – Committed – 45 Sec, Actual – 34 sec.

 

7. Steel plant– Blower

Motor Details: – Frame – YKS-800-4 Motor – 4550 KW, 6600V, 1493 rpm.

Blower: – Flow rate 1330 m3/min, For Sinter plant.

Power Transformer: – 20 MVA with int imp – 10.3%

FCMA-Soft starter Model No: FCMA- N-4500-6.6KV-40KA1-01-HD.

Performance Figures: –

Starting Current: – Committed by LEPL – 1602 amp, 3.6 I_fl

Achieved by us: – 1456 amp, 3.27 I_fl

Acceleration Time: – 45 Sec.

Volt drop: – less than 5 %

Please send us an enquiry via online custard Chat and Download a copy of Product Flyer by